Denox process / Denitrification

Denox process / Denitrification

CEMS II e

CEMS II e

  • description
  • technical data
  • download
description

The Gasmet Continuous Emission Monitoring System CEMS II e offers a TÜV/MCERTS-certified solution (QAL1) for a wide range of applications in the field of process and emission monitoring. Since all components are heated to 180°C, this extractive system is ideal for measuring gas components from hot, wet and corrosive gas streams.

A typical application is the simultaneous measurement of the following 16 gases to assess the emissions of an incinerator: H2O, CO2, CO, N2O, NO,NO 2, SO2, HCl, HF, NH3, CH4, C2H6, C3H8, C6H14, C2H4 and CH2O.

The CEMS II e is a modular system, usually consisting of the Gasmet CX4000 FTIR gas analyzer, a heated sampling unit with sampling probe, pump and filters, and an industrial PC with Calcmet software. If required, the CEMS II e can be equipped with a oxygen analyzer and/or a flame ionization detector GFID.

technical data
  • Measurement principles: Fourier transform infrared (FTIR) spectroscopy.
  • Measuring components: all IR-active gas components, 50 gas components can be measured simultaneously
  • Measuring ranges: from ppm to vol. %
  • Temperature measuring cell: 180°C
  • Optical length of the measuring cell: 500 cm
  • Output signal/interface: analogue outputs (4 - 20mA), digital outputs (24 VDC), freely programmable, optionally additional interfaces such as RS232 Modbus, Profibus etc.